Item NO.:
133819-01Order(MOQ):
1Goods Stock:
15Payment:
T/TLead Time:
In stockWeight:
0.4KGDimension:
2.6x11.2x24.2cmDescription:
I/O MODULEPrice:
AskBently Nevada · Verified configuration
3500/60 Temperature Monitor
Send the full part number, quantity, destination and available nameplate photos for a focused quotation review.
133819-01 is the rear-slot, internal-termination I/O module for a Bently Nevada 3500/60 Temperature Monitor. It brings RTD and thermocouple field signals into the six-channel monitor so temperature measurements can be processed within the 3500 machinery-protection platform.
133819-01 belongs to the non-isolated input configuration and may be configured for RTDs, thermocouples, or a permitted mix of both. It is the 3500/60 version without recorder outputs, making the exact monitor/I/O pairing and field-signal type the key checks before procurement.
Supports one through six RTD or thermocouple channels.
Field wiring terminates at the rear I/O module without a separate external termination block.
Provides temperature inputs for the 3500/60 monitor; this variant does not add recorder outputs.
| Manufacturer | Bently Nevada |
|---|---|
| Exact model | 133819-01 |
| Product family | 3500/60 Temperature Monitor |
| Module role | Rear I/O module |
| Input configuration | RTD/TC, non-isolated |
| Channel capacity | 6 channels |
| Termination | Internal |
| Recorder outputs | Not provided on 3500/60 |
| Rack position | One full-height rear slot |
| Operating temperature | -30°C to +65°C |
| Storage temperature | -40°C to +85°C |
| Official module dimensions | 241.3 × 24.4 × 99.1 mm |
| Official module mass | 0.45 kg |
Official module mass and dimensions describe the product itself. The commercial Weight and Dimension fields on this page are retained as the existing packing data unless the manufacturer publishes configured-package data.
This module is listed for the 3500/60, not the recorder-output 3500/61 configuration. A mismatched front monitor can invalidate the required signal path. Verify the front monitor identity and the complete part number before installation.
Select it for the 3500/60 internal-termination, non-isolated temperature configuration that does not require recorder outputs. Confirm the front monitor first.
Document the sensor type, range, polarity or lead arrangement for every channel and enter only a manufacturer-supported mix in the rack configuration.
No direct reuse should be assumed because this part uses internal terminations. Review and update the field-wiring design before selecting it.
Verify front-and-rear pairing, sensor type, terminal wiring, channel range, and rack configuration before enabling alarm functions.
Check the configured sensor type, lead or polarity, terminal tightness, field continuity, and channel range before replacing the module.
Provide the front 3500/60 number, sensor types by channel, internal-termination requirement, quantity, condition, destination, and clear labels.
Apter's 1 Year Warranty
Apter provides a 1-year warranty on every item we sell.
Our free 1-year warranty makes every Apter purchase a dependable, reliable investment in your company's future.
Apter sells industrial automation parts including new and discontinued products, and purchases such featured products through independent channels. Apter is not an authorized distributor, dealer or representative of the products featured on this site. All product names/product images, trademarks, brands and logos used on this website are the property of their respective owners. Product descriptions, depictions or sales with these names, images, trademarks, brands and logos are for identification purposes only and do not imply any affiliation or authorization to any rights holder.
Related Tags :